General information | | | |
Product type designation | CPU 414-2 | CPU 414-3 | CPU 414-3 PN/DP |
Hardware product version | 01 | 01 | 01 |
Firmware version | V7.0 | V7.0 | V7.0 |
Engineering with | | | |
| STEP 7 V5.4 or higher with HSP 261 | STEP 7 V5.4 or higher with HSP 261 | STEP 7 V5.5 or higher with HSP 262 |
CiR – Configuration in RUN | | | |
CiR synchronization time, basic load | 100 ms | 100 ms | 100 ms |
CiR synchronization time, time per I/O byte | 15 µs | 15 µs | 15 µs |
Supply voltage | | | |
Rated value (DC) | | | |
| No; Power supply via system power supply | No; Power supply via system power supply | No; Power supply via system power supply |
Input current | | | |
from backplane bus 5 V DC, typ. | 0.9 A | 1.1 A | 1.3 A |
from backplane bus 5 V DC, max. | 1.1 A | 1.3 A | 1.6 A |
from backplane bus 24 V DC, max. | 300 mA; 150 mA per DP interface | 450 mA; 150 mA per DP interface | 300 mA; 150 mA per DP interface |
from interface 5 V DC, max. | 90 mA; At each DP interface | 90 mA; At each DP interface | 90 mA; At each DP interface |
Power loss | | | |
Power loss, typ. | 4.5 W | 5.5 W | 6.5 W |
Power loss, max. | 5.5 W | 6.5 W | 8 W |
Memory | | | |
Type of memory | RAM | RAM | RAM |
Work memory | | | |
| 2 Mbyte | 4 Mbyte | 4 Mbyte |
| 1 Mbyte | 2 Mbyte | 2 Mbyte |
| 1 Mbyte | 2 Mbyte | 2 Mbyte |
| No | No | No |
Load memory | | | |
| Yes; with Memory Card (FLASH) | Yes; with Memory Card (FLASH) | Yes; with Memory Card (FLASH) |
| 64 Mbyte | 64 Mbyte | 64 Mbyte |
| 512 kbyte | 512 kbyte | 512 kbyte |
| Yes; with Memory Card (RAM) | Yes; with Memory Card (RAM) | Yes; with Memory Card (RAM) |
| 64 Mbyte | 64 Mbyte | 64 Mbyte |
Backup | | | |
| Yes | Yes | Yes |
| Yes; all data | Yes; all data | Yes; all data |
| No | No | No |
Battery | | | |
Backup battery | | | |
| 180 µA; up to 40 °C | 180 µA | 180 µA; up to 40 °C |
| 850 µA | 850 µA | 850 µA |
| Dealt with in the module data manual with the secondary conditions and the factors of influence | Dealt with in the module data manual with the secondary conditions and the factors of influence | Dealt with in the module data manual with the secondary conditions and the factors of influence |
| 5 V DC to 15 V DC | 5 V DC to 15 V DC | 5 V DC to 15 V DC |
CPU processing times | | | |
for bit operations, typ. | 18.75 ns | 18.75 ns | 18.75 ns |
for word operations, typ. | 18.75 ns | 18.75 ns | 18.75 ns |
for fixed point arithmetic, typ. | 18.75 ns | 18.75 ns | 18.75 ns |
for floating point arithmetic, typ. | 37.5 ns | 37.5 ns | 37.5 ns |
CPU-blocks | | | |
DB | | | |
| 6 000; Number range: 1 to 16000 | 6 000; Number range: 1 to 16000 | 6 000; Number range: 1 to 16000 |
| 64 kbyte | 64 kbyte | 64 kbyte |
FB | | | |
| 3 000; Number range: 0 to 7999 | 3 000; Number range: 0 to 7999 | 3 000; Number range: 0 to 7999 |
| 64 kbyte | 64 kbyte | 64 kbyte |
FC | | | |
| 3 000; Number range: 0 to 7999 | 3 000; Number range: 0 to 7999 | 3 000; Number range: 0 to 7999 |
| 64 kbyte | 64 kbyte | 64 kbyte |
OB | | | |
| see instruction list | see instruction list | see instruction list |
| 64 kbyte | 64 kbyte | 64 kbyte |
| 1; OB 1 | 1; OB 1 | 1; OB 1 |
| 4; OB 10-13 | 4; OB 10-13 | 4; OB 10-13 |
| 4; OB 20-23 | 4; OB 20-23 | 4; OB 20-23 |
| 4; OB 32-35 (shortest cycle that can be set = 500 µs) | 4; OB 32-35 (shortest cycle that can be set = 500 µs) | 4; OB 32, 33, 34, 35 (shortest cycle that can be set = 500 µs) |
| 4; OB 40-43 | 4; OB 40-43 | 4; OB 40-43 |
| 3; OB 55-57 | 3; OB 55-57 | 3; OB 55-57 |
| 3; OB 61-63 | 3; OB 61-63 | 3; OB 61-63 |
| 1; OB 60 | 1; OB 60 | 1; OB 60 |
| 1; OB 90 | 1; OB 90 | 1; OB 90 |
| 3; OB 100-102 | 3; OB 100-102 | 3; OB 100-102 |
| 9; OB 80-88 | 9; OB 80-88 | 9; OB 80-88 |
| 2; OB 121, 122 | 2; OB 121, 122 | 2; OB 121, 122 |
Nesting depth | | | |
| 24 | 24 | 24 |
| 1 | 1 | 1 |
Counters, timers and their retentivity | | | |
S7 counter | | | |
| 2 048 | 2 048 | 2 048 |
Retentivity | | | |
| Yes | Yes | Yes |
| 0 | 0 | 0 |
| 2 047 | 2 047 | 2 047 |
| Z 0 to Z 7 | Z 0 to Z 7 | Z 0 to Z 7 |
Counting range | | | |
| 0 | 0 | 0 |
| 999 | 999 | 999 |
IEC counter | | | |
| Unlimited (limited only by RAM capacity) | Unlimited (limited only by RAM capacity) | Unlimited (limited only by RAM capacity) |
S7 times | | | |
| 2 048 | 2 048 | 2 048 |
Retentivity | | | |
| Yes | Yes | Yes |
| 0 | 0 | 0 |
| 2 047 | 2 047 | 2 047 |
| No times retentive | No times retentive | No times retentive |
Time range | | | |
| 10 ms | 10 ms | 10 ms |
| 9 990 s | 9 990 s | 9 990 s |
IEC timer | | | |
| Yes | Yes | Yes |
| SFB | SFB | SFB |
| Unlimited (limited only by RAM capacity) | Unlimited (limited only by RAM capacity) | Unlimited (limited only by RAM capacity) |
Data areas and their retentivity | | | |
retentive data area in total | Total working and load memory (with backup battery) | Total working and load memory (with backup battery) | Total working and load memory (with backup battery) |
Flag | | | |
| 8 kbyte; Size of bit memory address area | 8 kbyte; Size of bit memory address area | 8 kbyte; Size of bit memory address area |
| Yes | Yes | Yes |
| MB 0 to MB 15 | MB 0 to MB 15 | MB 0 to MB 15 |
| 8; in 1 memory byte | 8; in 1 memory byte | 8; in 1 memory byte |
Data blocks | | | |
| 6 000; Number range: 1 to 16000 | 6 000; Number range: 1 to 16000 | 6 000; Number range: 1 to 16000 |
| 64 kbyte | 64 kbyte | 64 kbyte |
Local data | | | |
| 16 kbyte | 16 kbyte | 16 kbyte |
| 8 kbyte | 8 kbyte | 8 kbyte |
Address area | | | |
I/O address area | | | |
| 8 kbyte | 8 kbyte | 8 kbyte |
| 8 kbyte | 8 kbyte | 8 kbyte |
of which distributed | | | |
| 2 kbyte | 2 kbyte | 2 kbyte |
| 2 kbyte | 2 kbyte | 2 kbyte |
| 6 kbyte | 6 kbyte | 6 kbyte |
| 6 kbyte | 6 kbyte | 6 kbyte |
| | | 8 kbyte |
| | | 8 kbyte |
Process image | | | |
| 8 kbyte | 8 kbyte | 8 kbyte |
| 8 kbyte | 8 kbyte | 8 kbyte |
| 256 byte | 256 byte | 256 byte |
| 256 byte | 256 byte | 256 byte |
| 244 byte | 244 byte | 244 byte |
| Yes | Yes | Yes |
Subprocess images | | | |
| 15 | 15 | 15 |
Digital channels | | | |
| 65 536 | 65 536 | 65 536 |
| 65 536 | 65 536 | 65 536 |
| 65 536 | 65 536 | 65 536 |
| 65 536 | 65 536 | 65 536 |
Analog channels | | | |
| 4 096 | 4 096 | 4 096 |
| 4 096 | 4 096 | 4 096 |
| 4 096 | 4 096 | 4 096 |
| 4 096 | 4 096 | 4 096 |
Hardware configuration | | | |
Number of expansion units, max. | 21 | 21 | 21 |
connectable OPs | 63 | 63 | 63 |
Multicomputing | Yes; 4 CPUs max. (with UR1 or UR2) | Yes; 4 CPUs max. (with UR1 or UR2) | Yes; 4 CPUs max. (with UR1 or UR2) |
Interface modules | | | |
| 6 | 6 | 6 |
| 6 | 6 | 6 |
| 4; IM 463-2 | 4; IM 463-2 | 4; IM 463-2 |
Number of DP masters | | | |
| 2 | 2 | 1 |
| 10; CP 443-5 Extended | 10; CP 443-5 Extended | 10; CP 443-5 Extended |
| 4 | 4 | 4 |
| No; IM 467 cannot be used jointly with CP 443-5 Ext. or CP 443-1 in PROFINET IO mode | No; IM 467 cannot be used jointly with CP 443-5 Ext. or CP 443-1 in PROFINET IO mode | No; IM 467 cannot be used jointly with CP 443-5 Ext. or CP 443-1 in PROFINET IO mode |
| 0 | 1 | 1; IF 964-DP |
| 6 | 6 | 6 |
Number of IO Controllers | | | |
| 0 | 0 | 1 |
| 4; Max. 4 in the central controller; no mixed operation of different CP 443-1 types in PROFINET IO mode | 4; Max. 4 in the central controller; no mixed operation of different CP 443-1 types in PROFINET IO mode | 4; Max. 4 in the central controller; no mixed operation of different CP 443-1 types in PROFINET IO mode |
Number of operable FMs and CPs (recommended) | | | |
| Limited by number of slots and number of connections | Limited by number of slots and number of connections | Limited by number of slots and number of connections |
| CP 440: Limited by number of slots; CP 441: limited by number of connections | CP 440: Limited by number of slots; CP 441: limited by number of connections | CP 440: Limited by number of slots; CP 441: Limited by number of slots and number of connections |
| 14; In total max. 10 CPs as DP master and PROFINET controller, of which up to 10 IMs or CPs as DP master and up to 4 CPs as PROFINET controller | 14; In total max. 10 CPs as DP master and PROFINET controller, of which up to 10 IMs or CPs as DP master and up to 4 CPs as PROFINET controller | 14; In total max. 10 CPs as DP master and PROFINET controller, of which up to 10 IMs or CPs as DP master and up to 4 CPs as PROFINET controller |
Slots | | | |
| 1 | 2 | 2 |
Time of day | | | |
Clock | | | |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| 1 ms | 1 ms | 1 ms |
| 1.7 s; Power off | 1.7 s; Power off | 1.7 s; Power off |
| 8.6 s; For power On | 8.6 s; For power On | 8.6 s; For power On |
Operating hours counter | | | |
| 16 | 16 | 16 |
| 0 to 15 | 0 to 15 | 0 to 15 |
| SFCs 2, 3 and 4: 0 to 32767 hours SFC 101: 0 to 2^31 - 1 hours | SFCs 2, 3 and 4: 0 to 32767 hours SFC 101: 0 to 2^31 - 1 hours | SFCs 2, 3 and 4: 0 to 32767 hours SFC 101: 0 to 2^31 - 1 hours |
| 1 hour | 1 hour | 1 hour |
| Yes | Yes | Yes |
Clock synchronization | | | |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| No; Via CP | No; Via CP | Yes; As client |
| No | Yes | Yes |
Time difference in system when synchronizing via | | | |
| | | 10 ms |
| 200 ms | 200 ms | 200 ms |
Interfaces | | | |
Interfaces/bus type | 1 x MPI/PROFIBUS DP, 1 x PROFIBUS DP | 1 x MPI/PROFIBUS DP, 1 x PROFIBUS DP, 1 x PROFIBUS DP (optionally pluggable) | 1 x MPI/PROFIBUS DP, 1 x PROFINET (2 ports), 1 x PROFIBUS DP (optionally pluggable) |
Number of RS 485 interfaces | 2; Combined MPI / PROFIBUS DP and PROFIBUS DP | 2; Combined MPI / PROFIBUS DP and PROFIBUS DP | 1; Combined MPI / PROFIBUS DP |
Number of other interfaces | | 1; PROFIBUS DP with IF 964-DP (plug-in option; MLFB: 6ES7964-2AA04-0AB0) | 1; PROFIBUS DP with IF 964-DP (plug-in option; MLFB: 6ES7964-2AA04-0AB0) |
1. Interface | | | |
Interface type | Integrated | Integrated | Integrated |
Physics | RS 485 / PROFIBUS + MPI | RS 485 / PROFIBUS + MPI | RS 485 / PROFIBUS + MPI |
Isolated | Yes | Yes | Yes |
Power supply to interface (15 to 30 V DC), max. | 150 mA | 150 mA | 150 mA |
Number of connection resources | MPI: 32, DP: 16 | MPI: 32, DP: 16 | MPI: 32, DP: 16 |
Functionality | | | |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
MPI | | | |
| 32; If a diagnostics repeater is used on the line, the number of connection resources on the line is reduced by 1 | 32; If a diagnostics repeater is used on the line, the number of connection resources on the line is reduced by 1 | 32; If a diagnostics repeater is used on the line, the number of connection resources on the line is reduced by 1 |
| 12 Mbit/s | 12 Mbit/s | 12 Mbit/s |
Services | | | |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
DP master | | | |
| 16; If a diagnostics repeater is used on the line, the number of connection resources on the line is reduced by 1 | 16; If a diagnostics repeater is used on the line, the number of connection resources on the line is reduced by 1 | 16; If a diagnostics repeater is used on the line, the number of connection resources on the line is reduced by 1 |
| 12 Mbit/s | 12 Mbit/s | 12 Mbit/s |
| 32 | 32 | 32 |
Services | | | |
| Yes | Yes | Yes |
| Yes; S7 routing | Yes; S7 routing | Yes; S7 routing |
| No | No | No |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
Address area | | | |
| 2 kbyte | 2 kbyte | 2 kbyte |
| 2 kbyte | 2 kbyte | 2 kbyte |
User data per DP slave | | | |
| 244 byte | 244 byte | 244 byte |
| 244 byte | 244 byte | 244 byte |
| 244 byte | 244 byte | 244 byte |
| 244 | 244 | 244 |
| 128 byte | 128 byte | 128 byte |
DP slave | | | |
| 16 | 16 | 16 |
| http://support.automation.siemens.com/WW/view/en/113652 | http://support.automation.siemens.com/WW/view/en/113652 | http://support.automation.siemens.com/WW/view/en/113652 |
| 12 Mbit/s | 12 Mbit/s | 12 Mbit/s |
| No | No | No |
| 32; Virtual slots | 32; Virtual slots | 32; Virtual slots |
| 32 byte | 32 byte | 32 byte |
| 32 byte | 32 byte | 32 byte |
Services | | | |
| Yes; with interface active | Yes; with interface active | Yes; with interface active |
| Yes; with interface active | Yes; with interface active | Yes; with interface active |
| No | No | No |
| No | No | No |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| No | No | No |
| No | No | No |
Transfer memory | | | |
| 244 byte | 244 byte | 244 byte |